Add to Cart
Mobile Transformer Insulation Oil Purifier , With Trailer Mounted , Double Stages Vacuum
I. Products Description
Dissolved gasses in transformer oil can cause arcing, corona discharges, and overheating--reducing the electrical efficiency and lifetime of the transformer. Likewise, water contamination at levels as low as 30 ppm (parts per million) can adversely affect the insulating strength of the oil. With ever-increasing standards for energy efficiency of power distribution transformers, the need to effectively degas will become even more important in the future. particles contamination will also affect the function of insulating oil. So we need to clean used transformer oil.
Double Transformer Oil Purifier (DTOP SERIES )with Trailer Mounted is mainly used to improve the properties of insulation oil for 66KV to 500KV project. It can remove trace water, gas, particulate matters etc. from the insulating oil effectively and rapidly so as to boost performance of transformers, circuit breakers, mutual inductors, cable and capacitors which has insulation system.DTOP series Double Stage High Vacuum Transformer Oil Purifying Machine With Trailer specialize in purifying branded oil, insulating oil of high voltage and super high voltage transformer. Additionally, it is suitable for treating low viscosity lubrication oil. Dissolved gasses in transformer oil can cause arcing, corona discharges, and overheating--reducing the electrical efficiency.
II. Advantage
III.Technical parameters of Transformer Oil Purifier with Trailer Mounted
Item | Parameter |
Type Unit |
DTOP-1.8 | DTOP-3 | DTOP-6 | DTOP-9 | DTOP-12 | DTOP-18 | |
Technical Parameter | Flow Rate | L/H | 1800 | 3000 | 6000 | 9000 | 12000 | 18000 | |
Working Vacuity | Pa | ≤80 | |||||||
Working Pressure | Mpa | ≤0.35 | |||||||
Temperature Range | oC | 45-65 | |||||||
Power Supply | 50Hz 380V 3-Phase 4-Wire (or as requested) | ||||||||
Total Power | KW | 18+2.25 | 30+6 | 2X30+6.6 | 3X30+8.2 | 4X30+10 | 5X30+16.5 | ||
Inlet/Outlet Diameter | mm | 32 / 25 | 38 / 32 | 44 / 38 | 48 / 44 | 64 / 48 | 76 / 64 | ||
Size |
Length | mm | 1200 | 1500 | 1870 | 1930 | 2160 | 2250 | |
Width | mm | 950 | 1150 | 1250 | 1400 | 1600 | 1750 | ||
Height | mm | 1600 | 2000 | 2200 | 2460 | 2650 | 2650 | ||
Weight | Kg | 650 | 900 | 1200 | 1600 | 2200 | 3000 | ||
Oil Treatment Index | Breakdown Voltage | KV | 70-75 | ||||||
Water Content | ppm | 3~5 | |||||||
Gas Content | % | ≤0.2 | |||||||
Filtering Accuracy | µm | 1~3 |